Short answer
At business premises in England, oil stored in a container of more than 200 litres needs secondary containment, usually a bund.
The bund must hold at least 110% of the tank's capacity.
Where there are several tanks in one bund, it must hold 110% of the largest or 25% of the total, whichever is bigger.
Wales, Scotland and Northern Ireland have their own rules.
On this page
This post answers a question that comes up on almost every oil-fired boiler hire: what do the rules say about the fuel tank? The short version is that above 200 litres at a business, the tank needs a bund. The detail matters, though, so here it is.
Who the rules apply to
Most people think of oil storage rules as something for farms and fuel depots. In fact the England regulations apply to oil stored at almost any business, school, hospital or public building, as long as the container holds more than 200 litres.
The law is the Control of Pollution (Oil Storage) (England) Regulations 2001. “Oil” here covers the fuels you would expect, including diesel, gas oil and kerosene. GOV.UK sets out the rules in plain language on its oil storage page.
So if a hired boiler arrives with a 1,000 litre diesel tank and stands in your school car park for a term, the rules apply to that tank.
The bund: 110% and 25%
The heart of the regulations is secondary containment. That means a second skin or a walled area, called a bund, that catches the oil if the tank leaks or is overfilled.
The size rules are simple to state:
- One tank: the bund must hold at least 110% of the tank’s capacity.
- Several tanks in one bund: it must hold at least 110% of the largest tank, or 25% of the total capacity, whichever is greater.
The extra 10% is there for rainwater already sitting in an open bund, and for the surge when a tank fails suddenly. In other words, a bund that only just matches the tank is not enough.
How the numbers work
Here is a worked example for a site that has its own heating oil tank and is adding a hire boiler’s tank in the same bunded area:
| Tank | Capacity |
|---|---|
| Existing heating oil tank | 2,500 litres |
| Hire boiler’s tank | 1,500 litres |
| Total | 4,000 litres |
110% of the largest tank is 2,750 litres. 25% of the total is 1,000 litres. The bigger figure wins, so the shared bund must hold at least 2,750 litres.
In practice hire tanks usually arrive as self-bunded tanks, with the bund built in as an outer skin. That avoids the shared-bund sum altogether, and it is worth asking for.
What else the regulations expect
The bund is the part everyone remembers, but it is not the only requirement.
The regulations also cover:
- The tank itself, which must be strong enough not to burst or leak in ordinary use.
- Where it stands, away from anything likely to damage it, such as vehicle routes.
- Fittings, so that taps, valves, sight gauges and fill points sit inside the bund or are protected.
- Mobile bowsers, which have their own set of requirements in the England regulations.
If a delivery vehicle has to fill the tank, think about where it will park and how far the hose reaches. A spill at the fill point is one of the most common ways oil escapes.
Wales, Scotland and Northern Ireland
The rules above are for England. Wales has its own regulations, made in 2016, which follow a similar approach. Scotland and Northern Ireland have their own oil storage rules too, and NetRegs explains them for businesses there.
If your site is outside England, check the rules for that nation rather than assuming the English figures apply. The principle is the same everywhere: keep the oil out of the ground and the drains.
What this means when you hire a boiler
An oil-fired hire boiler is one of the easiest ways to get heat into a building with no suitable gas supply. The fuel tank is part of the package, so the hire firm should be able to answer these questions straight away:
- Is the tank bunded, and to what capacity?
- Who arranges fuel deliveries, and where will the vehicle stand?
- What happens to any oil left at the end of the hire?
Fuel itself is normally charged separately from the weekly hire. Our hire costs page explains how the rest of a quote is put together.
Getting it right first time
The Environment Agency can act where oil storage breaks the rules, and a spill into a drain is far more expensive than any bund. With a hired unit the fix is easy: ask for a bunded tank in writing, and agree where it will stand before delivery day.
If you are arranging oil-fired boiler hire and want a firm that supplies bunded tanks as standard, tell us about the site below.