Boiler Hire Sizing Calculator

Enter the building's size and how well it holds heat. You get a rough heat load in kilowatts, the next standard hire size up, and the supply that size usually needs. It is a rough first sizing; the hire firm confirms it on survey.

Hot water adds our rough 10% allowance.

Your rough first sizing

Estimated heat load

65 kW

Next standard hire size up
80 kW
Supply it usually needs
How we got there

This is a rough first sizing, not a specification. The hire firm confirms the size, the supply and the connection when it surveys the site.

How the rough sizing works

Most people expect boiler sizing to start from floor area alone. In practice it is the volume of air you are heating, how fast the building loses heat, and how cold it gets outside that matter. The calculator multiplies those together.

In other words: volume (floor area times ceiling height), times a heat loss factor for how leaky the building is, times the difference between the inside and outside temperatures. That gives watts, and dividing by 1,000 gives kilowatts.

A building drawn as a box: floor area times ceiling height gives volume; volume times a heat loss factor times the temperature difference gives a rough heat loadfloor area 1,000 m²3 m21 °Cinside−3 °Coutside, cold dayVolume1,000 × 3 = 3,000 m³Heat load3,000 × 0.9 × 24= 64,800 W ≈ 65 kWNext hire size: 80 kW
The office example from the calculator, using our rough heat loss factor for an average building (0.9 W per m³ per °C). A rough first sizing only; the hire firm confirms on survey.

The heat loss factors are our own rule-of-thumb bands, not figures from a standard. We use lower factors for tall, open buildings such as warehouses, because so much of their volume sits high up and they tend to be kept cooler. A proper heat loss calculation works room by room from the walls, roof, glazing and air changes, and that is the hire firm's job on survey.

Standard hire sizes and the supply they need

Hire firms keep set sizes rather than building a unit to order, so the calculator moves your load up to the next one. These are the packaged sizes UK fleets commonly list:

Unit sizeUsual formSupply commonly needed
3 to 36 kWMobile electric boilerRoughly its own output in electrical power
80 kWSmall packaged unitAsk the hire firm
100, 250 and 300 kWSlimline unitSingle-phase 16 A
375, 500, 1,250 and 1,500 kWPackaged boiler, often containerised or on a trailerThree-phase 32 A
Above 1,500 kWSeveral units coupled togetherOne supply per unit

The supply here is for the burner, controls and pumps on a gas or oil unit, not for the heat itself. An electric boiler is different: it turns electricity straight into heat, so it needs a supply big enough for its whole output. That is why electric hire tends to stop at small sizes.

Check the figure against what you already have

If the building has a boiler already, it's very important to compare your result with the output on its data plate. Has the building been extended or insulated since the boiler went in? Then the old figure may be on the high side. Is one of two boilers already off? Then you may only need to cover half the load.

You may find that the calculator and the nameplate disagree by a size. That's normal, and it is exactly the kind of thing a hire firm settles on its site visit. Put both figures in your request and let them decide.

Sizing is half the conversation. For what goes into the weekly price, see what decides the cost of boiler hire, and for buildings that cannot be left cold for a day, read about emergency boiler hire.

Sources for this page

Heat loss factors and the hot water allowance are our own rough bands. Unit sizes and supplies are those UK hire fleets commonly list; they vary between firms.

Sizing questions

What is the quickest way to size a hire boiler?

Look at the data plate on the boiler you are replacing. Its rated output is usually the best single guide, because someone sized it for the building when it went in. If there are several boilers in the plant room, add their outputs together, then ask whether they all ran at once in cold weather.

Why does the calculator round up rather than to the nearest size?

A unit that is slightly too small cannot hold the building warm on the coldest days, while one a step bigger simply runs less hard. Hire firms list set sizes, so we move to the next size up from the load.

Should I hire one big boiler or two smaller ones?

Two smaller units give you something to fall back on if one trips, and they suit buildings with split circuits. One unit is simpler to place and connect. The calculator shows a two-unit option for bigger loads so you can ask the hire firm about both.

Does hot water change the size I need?

It can. If the hire boiler also heats a hot water cylinder or calorifier, it has to cover that load on top of the heating. We add a flat 10% as a rough allowance; a large kitchen, a pool or a care home with many showers may need more, so mention it in your request.

What temperature should I plan to hold inside?

For most workplaces the Approved Code of Practice says a workroom should normally be at least 16 °C, or 13 °C where the work involves severe physical effort (HSE). Offices, schools and care settings are usually kept warmer than that minimum, which is why the calculator starts most building types at 21 °C.

Send us your sizing

We find a boiler hire firm that covers your site and give you their name before any of your details go to them. It costs you nothing.

What happens next

  1. We look for a hire firm that covers your postcode and the size of unit you need.
  2. We give you the firm's name first. Your details only go to them if you say yes.
  3. The firm checks the site, confirms the size and sends a written price.